Home
Troubleshooting
Troubleshooting
Q
Alarm Code
A
Failure of liquid temperature sensor
More
Check
Check if the connection of the liquid temperature sensor is with broken cable or poor connection.
Main controller is broken if the above items are checked and good.
Trouble Shooting
Replace the new temperature sensor.
Replace the temperature controller.
Q
Alarm Code
A
Failure of ambient temperature sensor
More
Check
Check if the connection of the ambient temperature sensor is with broken cable or poor connection.
Main controller is broken if the above items are checked and good.
Trouble Shooting
Replace with ambient temperature sensor.
Replace with temperature controller.
Q
Alarm Code
A
Over current of compressor
More
Check
Check if the input power voltage is correct.
Check if the compressor is burned out.
Check if the overload protector trips out.
Check if the temperature inner cooler unit is too high.
Check if the fan is out of order.
Trouble Shooting
Correct the input power voltage.
Replace with new compressor.
Reset the overload protector.
Improve the working environment to have better ventilation.
Replace with new fan.
Q
Alarm Code
A
Over current of pump motor
More
Check
Check if the pump motor operates normal.
Check if the shaft of pump is stuck or worn out.
Check if the pipe resistance if too big to cause the tripping of overload protector.
Check if the pipe is blocked.
Trouble Shooting
Replace with new pump and motor.
Reset the overload protector after reduce pipe resistance.
Clean-up the liquid circulation system. Install a liquid filter if it is necessary.
Q
Alarm Code
A
Failure of flow rate
More
Check
Check if there is liquid level in tank and flow in pipe shall be sufficient.
Flow loss may be caused by too long, small or squashed pipe.
No flow in pipe caused by failure of pump.
Flow is blocked due to air generated in pipe.
Flow switch is broken if the above items are checked and good.
Trouble Shooting
Fill water to tank and pipes.
Shorten the length of pipe or use pipe with proper diameter.
Replace with new pump and motor.
Release the air in pipe.
Replace faulty parts.
Q
Alarm Code
A
Failure of high temperature in compressor
More
Check
Check if it is blocked at air intake and exhaust of cooler unit.
Check if the input voltage and power phase is correct.
Check the compressor condition and power voltage at the time of start working.
Trouble Shooting
Improve the environment ventilation.
Correct power phase and voltage.
Replace with new compressor.
Q
Alarm Code
A
Abnormal pressure
More
Check
The temperature is not cold at the pipe of low pressure side of compressor.
The temperature of the dryer surface is lower than exhaust heat.
The temperature on dryer housing is too low.
Check if the temperature inner cooler unit is too high.
Check if fan motor is broken.
Trouble Shooting
Please contact the certified service technician for the repair of refrigeration system.
Clean the air filter and the condenser regularly to improve the heat dissipation, and remove any obstructers from air intake or exhaust.
Q
Alarm Code
A
Over current of fan motor
More
Check
Check the overload protection.
Check if the fan motor is failure.
Trouble Shooting
Reset the overload protector.
Replace with new fan motor.
1
2
3
TOP
?